Installation/configuration notes
Compatible Products
The following products are compatible with the
DS7080iP-32 Control Panels:
Keypads and
Annunciators
DS7443S LED Keypad
DS7445i LED Keypad
DS7445V2 LED Keypad
DS7447E LCD Keypad
DS7447V2 LCD Keypad
Modules C900 Dialer Capture Module
C900TTL-E Dialer Capture Module
DS7480 Bell Supervision Module
DS7481 Single Phone Line Monitor
DS7488 Octal Relay Module
DS7489 Solid-state Output Module
Technical specifications
Communicator
Phone Numbers: 2 phone numbers are available for
reporting. A third number is available
for remote programming.
Report Formats: Full single, double and backup
reporting
Communication Formats: SIA, 3/1 Ext, 4/1, 4/2, Contact ID,
High Speed 4/9, BFSK, and pager
format
Ringer Equivalence: 0.1 B
Enclosure
Material: 1.0 mm, cold-rolled steel
Dimensions: 32 cm x 37 cm x 7.6 cm
Environmental Considerations
Relative Humidity: 5% to 85% at +30°C non-condensing
Temperature (Operating): 0°C to +49°C
Fire Signal Initiating Circuit (Two-Wire Mode)
Circuit Type: Class B, latching
Supervisory Current: 5 mA
Circuit Voltage: 8.5 VDC to 14.1 VDC
Circuit Resistance: 60 Ω maximum
Current for Alarm: 12 mA minimum
Impedance for Alarm: 1000 Ω maximum
Short Circuit Current: 22 mA maximum
Detector Standby Current: 2.5 mA total
Detectors per Zone: 20 detectors (two-wire) maximum
Inputs
Burglar/Fire Zone: 8 circuits on-board, 24 off-board zones
can be added.
End-of-line resistor: 2.21 kΩ (P/N:
19809)
System Trouble: A separate terminal can be used to
monitor multiple external devices such
as phone line monitors, without using 1
of the 8 zones. A dry contact output
from such a device causes a system
trouble.
Keypads
Keypads: 4 maximum
Outputs
Alarm Output: Normally-open, 1.0 A contact
connected to auxiliary power. Can be
programmed for steady or pulsed
output.
Programmable Output 1: Solid-state current sink (500 mA
maximum) can be used for alarm,
arming state, or access control. This
output is generally programmable.
Programmable Output 2: Solid-state voltage source (500 mA
maximum). This is the smoke power
reset for Zone 1 when it is used as a fire
zone for two-wire smoke detectors.
Can be used for alarm, arming state, or
access control.
Power Requirements
Input Power: 18 VAC, 50 VA, 50 Hz
Output Power: 1.5 A maximum
Auxiliary Power: 10.2 VDC to 14.1 VDC
Auxiliary Current: Total current for all auxiliary devices,
including keypads and smoke
detectors, is 1.0 A standby and 1.5 A
alarm.
Panel Standby Current: 115 mA
Ordering information
DS7080IP32‑EXP Control Panel
For export. Includes one control panel for 220 VAC
operation, one enclosure, one lock set, one
transformer, one resistor, and one hardware pack.
Order number DS7080IP32-EXP
3 | DS7080iP32 Eight-zone Control Panels