DS7060-AUS Reference Guide Copyright 1997-98 Detection Systems, Inc. Page 11
• Duress Code:
If this option is selected and Code
14 is used to disarm the system, a duress report will
be sent as the system is otherwise disarmed
normally. User Code 14 will not arm the system, or
report duress, if the system is not armed.
• Guest Code:
If this option is selected, Code 15 is
a guest code. It can be enabled by pressing [PIN]
[#] [8] [4]. It will remain active until the panel is
disarmed with any other valid code.
• Arming Warning:
If this option is selected, the
alarm output will turn on for 2 seconds when the
panel is armed.
• Keypad Audible During Exit Delay:
Selection of
this option will cause the keypad sounders to beep
during the exit delay time. A one second beep will
sound at 5 second intervals, changing to a 3-beep
tone at 10 and 5 seconds prior to the end of the
delay.
• Keyswitch Arming Warning:
Selecting this option
will activate any output programmed as Intrusion,
Follow Burg Alarm, or Follow Burg Alarm and Fire
Alarm. The output will beep once (200 ms ON)
when a keyswitch toggle zone arms the system. A
double beep will occur (200 ms ON-OFF-ON) when
a keyswitch toggle zone disarms the system.
• Siren on Comm. Fail for Silent Zone: If
programmed, a silent zone will sound the alarm
outputs if the zone is in an alarm condition and the
system fails to communicate with the central
station.
• Closing Ringback: If programmed, the keypad
sounders and Output 3 will activate for 2 seconds
after the system is armed and the closing report is
successfully sent. This requires Closing Ringback
and Closing Report to be programmed. If the panel
does not report to a central station, use “Arming
Warning” in Address 9.
• Swinger Shunt: If enabled, a zone can only alarm
or trouble up to three times per armed period. After
the third alarm or trouble, the zone will be bypassed
and a bypass report for this zone will be sent. Fire
zones are never swinger shunted.
• 50 Hz/60 Hz: Set to local power type. The panel
clock is synchronized to the power line frequency.
60 Hz required for UL Listed Requirements.
• Keypad Mode: Commercial Mode requires a PIN
number for all functions. Residential Mode only
requires a PIN number for disarming and silencing
alarms.
• Quick Arm: If enabled, a PIN is not needed to arm.
Note: Used only in conjunction with commercial
mode.